White-Rodgers 1F87-0261 Programmable (7 day) Thermostat
About This Thermostat
MFG: | White-Rodgers |
MFG#: | 1F87-0261 |
Our#: | 175778 |
Programmable: | Yes (7 Day) |
Stages: | 1H & 1C |
System Compatibility: | Single Stage |
Power Options: | Battery, 24 VAC Hardwire |
Heat/Cool Changeover: | Manual |
Programmable Fan: | No |
Temperature Limits: | No |
Keypad Lockout: | No |
Backlight: | Yes |
Vacation Hold: | No |
White-Rodgers 1F87-0261 Programmable (7 day) Thermostat uses the technology of a solid-state microcomputer to provide precise time/temperature control, as well as offer you the flexibility to design heating and cooling programs that fit your needs - Replaces 1F87-361
Suitable for conventional 1 Heat / 1 Cool HVAC systems
FEATURES:
Programmable
- Programmable in 7 Day
- 4 time and 4 temperature settings per program (heat & cool)
- Energy savings up to 33%
- Patented pre-programmed software simplifies time and temperature programming
Display
- Easy-to-read LCD with improved contrast
- Lighted display for easier low-light viewing
Comfort & Convenience
- Permanent program retention during power loss
- Setpoint Hold
- Simple "setup" menu to activate optional features
- Temporary temperature override two-hour minimum or until next program period
- Soft-touch keypad
- Display temperature recalibration (+/- 4°)
- Easy access battery compartment
Performance
- Dual-Powered.choice of battery-powered or hardwired, for all applications
- Selectable Energy Management Recovery
- Meets ENERGY STAR® specifications
- Meets California Building Code, Title 24
- Fast (FA) or slow (SL) heating cycle anticipation
- Easy-to-wire push-connect color coded terminals
- Compressor lockout protection
- Millivolt compatible
- Electric heat option
SPECIFICATIONS
Electrical Rating:
Dual Power or Battery Power Model . . . . mV to 30 VAC, NEC Class II, 50/60 Hz or DC
Input-Hardwire Model . . . . . . . . . . . . . . . . 20 to 30 VAC
Terminal Load . . . . . . . . . . . . . . . . . . . . . . . 1.0 A per terminal,
1.5A maximum all terminals combined
Setpoint Temperature Range . . . . . . . . . . . 45 to 90°F (7 to 32°C)
Anticipation, Heating . . . . . . . . . . . . . . . . . . Adjustable
Anticipation, Cooling . . . . . . . . . . . . . . . . . . Fixed
Rated Differential, Heat . . . . . . . . . . . . . . . 0.8° or 1.2°F
Rated Differential, Cool . . . . . . . . . . . . . . . . 1.2°F
Operating Ambient Temperature Range . . . 32 to 105°F (0 to 44°C)
Operating Humidity Range . . . . . . . . . . . . . 0-90% RH noncondensing
Shipping Temperature Range . . . . . . . . . . . -40 to +150°F (-40 to +65°C)
Dimensions . . . . . . . . . . . . . . . . . . .3-3/4"H x 4-3/4"W x 1-1/2"D
Terminals: R, C, G, O/B, W, Y